Equipment Rated for 100 A or Less — NEC 110.14(C)(1)(a) items 1 through 4:

For equipment with termination provisions for circuits rated 100 A or less or marked for 14 AWG through 1 AWG conductors, the NEC allows conductors to be used based on the following four conditions:

  • Conductors rated for 60°C.
  • Conductors with higher temperature ratings can be used, but their ampacity must be based on the 60°C rating.
  • Conductors with higher temperature ratings are allowed if the equipment is listed and identified for use with those conductors.

Equipment Rated above 100 A — NEC 110.14(C)(1)(b) items 1 and 2

For equipment with termination provisions for circuits rated above 100 A or marked for conductors larger than 1 AWG, the NEC 110.14(C)(1)(b) items 1 and 2 allow conductors to be used based on the following conditions:

  • Conductors rated 75°C

  • Conductors with higher than 75°C can be used, but their ampacity must be based on the 75°C rating.

 