ADA Requirements (Accessible Units/Common Areas):

Review the reach range requirements for countertop receptacles per section 308 of the ADA code and section 1138A of the California Building Code. Coordinate with the architect.

https://up.codes/s/reach-ranges

https://up.codes/s/space-allowances-and-reach-ranges

Obstructed High Forward Reach:

ADA 308.2.2 Where a high forward reach is over an obstruction, the clear floor space shall extend beneath the element for a distance not less than the required reach depth over the obstruction.  The high forward reach shall be 48 inches (1220 mm) maximum where the reach depth is 20 inches (510 mm) maximum.  Where the reach depth exceeds 20 inches (510 mm), the high forward reach shall be 44 inches (1120 mm) maximum and the reach depth shall be 25 inches (635 mm) maximum.